Butcher Island fire: BPCL had no firefighting capability says report
Updated On: 31 May, 2018 09:17 AM IST | Vinod Kumar Menon
Safety committee that probed Butcher Island blaze of October 2017 finds initial firefighting was done by outsourced group, the water pressure was inadequate and, chiefly, that there was no disaster control room at the incident site

Firefighting operations went on for five days on the island
Serious lapses in procedure and protocol have come to light in the Oil Industry Safety Directorate (OISD) report on the fire that broke out in Tank No. 13 (Tank A) of Bharat Petroleum Corporation Limited (BPCL) on Butcher Island on October 6, 2017. OISDâÂu00c2u0080Âu00c2u0088is the petroleum ministry's regulatory and technical watchdog. The four-page report has, among other things, pointed to poor maintenance and almost no adherence to prescribed safety measures.
The report, prepared by a three-member OISD committee comprising V J Rao, executive director; M Gupta, additional director (refinery) and Pramod Kumar, joint director, found several lapses. Senior officers claim that had their concerns been taken seriously, such a situation would have been averted. They are keen to know what action will be taken on the basis of these findings.

The BPCL tank fire at Butcher Island in October last year
ADVERTISEMENT
Poll
Who will win the Punjab Elections?
Sources within the refinery, who got a preview of the OISD report, told mid-day that though OISD has tried to downplay the episode, it did touch upon a few areas of concern such as: a) initial fire fighting was carried out by an outsourced operating group that had limited experience of the oil and gas industry, b) the fire water header pressure was about 3.5 -4.5 kg/cm2g resulting in ineffective fire fighting initially, which was subsequently increased to 6-6.5 kg/cm2g, c) no Disaster Control Room set up at the site of the incident, d) the sprinkler system of adjacent tanks was working but had flange leakages and some of the spray nozzles were choked, e) CCTVs video of the fire could not be retrieved as the connected hard disk was faulty, f) The intensity of fire was reduced on the third night around 22 hours. However on the fourth day, the intensity of the flames increased and the fire was finally put out at 00.15 hours on the fifth day.
Tags
Trending Stories
Latest Web Stories
Latest Photos
06 August, 2026 08:34 PM IST | In Photos: Hiroshima Day Silent Peace March 2026
Preshit Deorukhkar
17 December, 2025 11:56 AM IST | IN PHOTOS: MLAs at Vidhan Bhavan during Maharashtra Legislative Council polls
Asif Ali Sayed
09 September, 2024 09:32 PM IST | IN PHOTOS: People in Mumbai celebrate Gauri Puja during Ganeshotsav
Asif Ali Sayed
09 September, 2024 09:13 PM IST | IN PHOTOS: Mumbai witnesses sunny weather as rains take a break
Asif Ali Sayed
Latest Videos
ADVERTISEMENT
Mid-day Fast
Latest Headlines
23 August, 2026 09:06 AM IST | mid-day online correspondent
20 August, 2026 09:25 PM IST | mid-day online correspondent
19 August, 2026 07:14 PM IST | Makepeace Sitlhou
19 August, 2026 11:50 AM IST | Test Tushar